Printer Friendly Version of Installation Guide

Roto-Phase Installation Guide

Printable Wiring Diagram (PDF)

Pre-Installation Instructions

Bulletin #125 9/99

INSPECTION

Upon receiving the Roto-Phase, inspect for damage or missing parts and report such losses to the carrier and to the factory; always quoting the Roto-Phase model and serial number.

INSTALLATION

The Roto-Phase is suitable for mounting in any position, horizontal or vertical. Care must be taken when mounting to wall, rafters, or wood floors to make sure that normal Roto-Phase vibration is not transmitted with sounding board amplification.

AVOIDING MAINTENANCE

The Roto-Phase is an essentially reliable machine and requires little maintenance; in fact they tend to suffer from over attention more than inattention. Avoid whenever possible.

  1. Moisture and Chemicals
  2. Airborne materials that may cause blocked ventilation, which leads to excessive heat. Cooling air temperatures must not exceed 40 degrees Celcius (104 Degrees Farenheit).

LUBRICATION

All models (since 1976) have double shielded bearings and do not need lubrication.

INSTALLATION INSTRUCTIONS

GENERAL HOOK-UP, FOLLOW ALL LOCAL, STATE & NATIONAL ELECTRIC CODES

  • Connect L1 & L2 through a separate protective device to Roto-Phase Terminal Block T1 & T2. (For wire sizes see "Roto-Phase Input" chart).
  • Connect Roto-Phase lead T3 (mfg.phase) through the separate protective device to the 3-phase distribution panel and/or 3 phase motors.
  • Connect L1 & L2 (single phase) to 3-phase distribution panel and/or 3 phase motors.
  • If your Roto-Phase contains an auxiliary capacitor panel with connection circuits B & E, refer to connection diagram for proper installation.

PRECAUTIONS

  • Do not connect any single-phase load or magnetic controls to T3 (mfg.phase). T3 can be readily identified by the line with the highest phase to ground voltage.
  • Properly ground all electrical equipment.
  • Always start Roto-Phase before energizing motors.
  • Because properly maintained voltages on motor starts is very important, wire sizings must be carefully followed and wire distances should also be carefully studied.

SPECIAL INSTRUCTIONS

Non-PCB capacitors are standards established by Federal Regulation

The no-load amperage readings are typical of normal operations. They may vary approximately 10% with variation of line voltage. Reasonably close readings insure correct Roto-Phase electrical performance.

T1 = Line current

T2 = Line current

T3 = Capacitor current

At the time of original installation, record the Roto-Phase no-load amperage (no motors running) as well as the capacitor amperage. To read capacitor amperage, it will be necessary to read the capacitor circuits in the capacitor panel, which will require removing the panel cover.

Save this record and periodically (at least once a year) have a qualified electrician take new readings, comparing these new readings with the original readings.

If capacitor amperage is lower than originally, it means that a capacitor has probably failed and should be replaced.

Phase converters cannot be made to work equally well on all motors, even though the horsepower and voltage ratings are the same. Motors of different make and designed for different purposes, vary considerably in their electrical characteristics. Therefore, it is not always possible to make a universally applicable converter for motors with a given horsepower and voltage rating.

HELPFUL HINTS

NOTE: All ROTO-PHASE models should be up to full speed within 3 – 4 seconds.

If nothing starts:

  1. Check voltage supply source with voltmeter.
  2. Check protection-reset breaker or replace fuses.
  3. Check for loose connections.

If ROTO-PHASE will not start or comes up to speed slowly:

  1. Check single phase input lines (L1 & L2) for misconnection. (L1 & L2 must connect to ROTO-PHASE T1 & T2).
  2. Capacitors may be disconnected from circuit or defective.
  3. Check for wrong supply voltage: Example: 46 VAC unit connect to 230 VAC supply.
  4. Check for locked bearing(s).

If fuses blow or circuit breaker trips:

  1. Check to be sure fuses are "TIME DELAY" (Dual Element) and correct size.
  2. Check to be sure circuit breakers are designed to handle starting currents, "HVAC" design.

If ROTO-PHASE is "noisy":

  1. Check for loose panel or panel lid.
  2. Be sure unit is mounted on level floor.
  3. Sometimes grease in bearings can make intermittent noise, which sounds like a bearing, but is not and usually, smoothes out after a short run period – (10 to 15 minutes).

If motor does not come up to full speed:

  1. Excessive single-phase voltage drop is evident. Voltage should not drop below 215 VAC on motor starting from a 230 VAC supply. A 20 VAC drop may indicate the wire size is too small (undersized), or utility company’s transformer is too small.
  2. Starting torque required is too great:
    • Mechanical problems with motor equipment.
    • In case of compressors, the unloading device may be inoperative, starting against head pressure.

RECORD FOR NO-LOAD ROTO-PHASE ELECTRICAL READINGS

 

DATE OF INSTALLATION:_______________________________

Roto-Phase Model Number:_________________________________

Roto-Phase Serial Number:__________________________________

Phase 1 to Ground:________________________________________Volts

Phase 2 to Ground:________________________________________Volts

Phase 3 to Ground:________________________________________Volts

Phase 1 to Phase 2:________________________________________Volts

Phase 1 to Phase 3:________________________________________Volts

Phase 2 to Phase 3:________________________________________Volts

Phase 1 Amperage:______________________

Phase 2 Amperage:______________________

Phase 3 Amperage:______________________Capacitor Wires

Model Specifications:
Standard Roto-Phase I Automatic Roto-Phase
Heavy Duty Roto-Phase II SP Series Roto-Phase
Light Duty Roto-Phase III Current Limiting Roto-Phase
Center Pivot Roto-Phase Passenger and Freight Elevator Roto-Phase
CNC Roto-Phase TM Series Roto-Phase
HDH Roto-Phase Computer Load Roto-Phase

Standard Duty Roto-Phase I
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
MF 12 12 10 5 10 5 0 0 2.5 1.25 3.9 1.95
MG 12 12 10 5 10 5 0 0 2.5 1.25 8.5 4.25
M 12 12 15 8 15 8 0 0 3 1.5 13 6.5
A 8 12 30 15 30 15 1 0 4 2 22 11
R 8 10 40 20 40 20 2 1 7 3.5 33 16.5
B 6 10 50 25 45 22 2 1 7 3.5 40 20
C 4 8 80 40 60 30 3 2 11 5.5 61 30.5
G 3 6 100 50 80 40 3 2 16 8 80 40
P 2 6 125 60 100 50 3 2 18 9 110 55
PKT 2 6 125 60 100 50 3 2 18 9 110 55
PKO 2 6 125 60 100 50 3 2 18 9 110 55
K2G* 3* 6 100* 50* 80* 40* 3* 2* 16* 8* 80* 40*
Y2P* 2* 6* 125* 60* 100* 50* 3* 2* 18* 9* 110* 55*
L2S* 1/0* 4* 150* 75* 125* 60* 4* 2* 23* 11.5* 128* 64*
W3P* 2* 6* 125* 60* 100* 50* 3* 2* 18* 9* 110* 55*
*Indicates units in electrical parallel. Data represents requirements for each unit.

Heavy Duty Roto-Phase II
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
HD2 12 12 15 8 15 8 0 0 3 1.5 13 6.5
HD3 10 12 20 10 20 10 0 0 5 2.5 16 8
HD5 8 10 40 20 40 20 2 1 7 3.5 33 16.5
HD7 6 10 50 25 45 22.5 2 1 7 3.5 40 20
HD10 4 8 80 40 60 30 3 2 11 5.5 61 30.5
HD15 3 6 100 50 80 40 3 2 16 8 80 40
HD20 2 6 125 60 100 50 3 2 18 9 110 55
HD25 1/0 4 150 75 125 60 4 2 23 11.5 128 64
HD30 1/0 4 150 75 125 60 4 2 23 11.5 128 64
HD40 1/0 4 150 75 125 60 4 2 23 11.5 128 64
HD2P* 2* 6* 125* 60* 100* 50* 3* 2* 18* 9* 110* 55*
HD2S* 1/0* 4* 150* 75* 125* 60* 4* 2* 23* 11.5* 128* 64*
HD3P* 2* 6* 125* 60* 100* 50* 3* 2* 18* 9* 110* 55*
HD4P* 2* 6* 125* 60* 100* 50* 3* 2* 18* 9* 110* 55*
*Indicates units in electrical parallel. Data represents requirements for each unit.

Light Duty Roto-Phase III
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
ST3 12 12 10 5 10 5 0 0 2.5 1.25 3.9 1.95
ST5 10 12 20 10 20 10 0 0 5 2.5 16 8
ST7 8 12 30 15 30 15 1 0 4 2 22 11
ST10 8 10 40 20 40 20 2 1 7 3.5 33 16.5
ST15 6 10 50 25 45 22.5 2 1 7 3.5 40 20
ST20 4 8 80 40 60 30 3 2 11 5.5 61 30.5

Center Pivot Roto-Phase
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
PV0 12 12 15 8 15 8 0 0 3 1.5 13 6.5
PV1 8 12 30 15 30 15 1 0 4 2 22 11
PV2 8 10 40 20 40 20 2 1 7 3.5 33 16.5
PV3 6 10 50 25 45 22 2 1 7 3.5 40 20
PV4 4 8 80 40 60 30 3 2 11 5.5 61 30.5
PV5 3 6 100 50 80 40 3 2 16 8 80 40
PV6 2 6 125 60 100 50 3 2 18 9 110 55
PV7 1/0 4 150 75 125 60 4 2 23 11.5 128 64
PV8 1/0 4 150 75 125 60 4 2 23 11.5 128 64
PV9 1/0 4 150 75 125 60 4 2 23 11.5 128 64
PV10 1/0 4 150 75 125 60 4 2 23 11.5 128 64

CNC Roto-Phase
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
CNC1 12 12 15 8 15 8 0 0 5 2.5 7 3.5
CNC2 8 12 30 15 30 15 1 0 6 3 11 5.5
CNC3 8 10 40 20 40 20 2 1 8 4 24 12
CNC5 6 10 50 25 45 22.5 2 1 10 5 26 13
CNC7 4 8 80 40 60 30 3 2 12 6 28 14
CNC10 3 6 100 50 80 40 3 2 16 8 60 30
CNC15 1/0 4 150 75 125 60 4 2 22 11 86 43
CNC20 3* 6* 100* 50* 80* 40* 3* 2* 16* 8* 60* 30*
CNC25 2* 6* 125* 60* 100* 50* 3* 2* 20* 10* 78* 39*
CNC30 1/0* 4* 150* 75* 125* 60* 4* 2* 22* 11* 86* 43*
*Indicates units in electrical parallel. Data represents requirements for each unit.

HDH Roto-Phase
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
HDH1 12 12 15 8 15 8 0 0 3 1.5 1.5 0.75
HDH2 8 12 30 15 30 15 1 0 4 2 2 1
HDH3 8 10 40 20 40 20 2 1 7 3.5 3.5 1.75
HDH5 6 10 50 25 45 22.5 2 1 7 3.5 3.5 1.75
HDH7 4 8 80 40 60 30 3 2 11 5.5 5.5 2.75
HDH10 3 6 100 50 80 40 3 2 16 8 80 40
HDH15 1/0 4 150 75 125 60 4 2 23 11.5 128 64

Automatic Roto-Phase
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
CMG 12 12 10 5 10 5 0 0 2.5 1.25 1.2 0.6
CMG 12 12 15 7.5 15 7.5 0 0 3 1.5 1.5 0.75
CA 8 12 30 15 30 15 1 0 4 2 2 1
CR 8 10 40 20 40 20 2 1 7 3.5 3.5 1.75
CB 6 10 50 25 45 22.5 2 1 7 3.5 3.5 1.75
CC3 4 8 80 40 60 30 3 2 11 5.5 5.5 2.75
CG 3 6 100 50 80 40 3 2 16 8 8 4
CP 2 6 125 60 100 50 3 2 18 9 9 4.5
CS 1/0 4 150 75 125 60 4 2 23 11.5 11.5 5.75
DBM 12 12 15 7.5 15 7.5 0 0 3 1.5 1.5 0.75
DBH 10 12 20 10 20 10 0 0 5 2.5 2.5 1.25
DBA 8 12 30 15 30 15 1 0 4 2 2 1
DBR 8 10 40 20 40 20 2 1 7 3.5 3.5 1.75
DBB 6 10 50 25 45 22.5 2 1 7 3.5 3.5 1.75
DBC 4 8 80 40 60 30 3 2 11 5.5 5.5 2.75
DBG 3 6 100 50 80 40 3 2 16 8 8 4
DBP 2 6 125 60 100 50 3 2 18 9 9 4.5
DBS 1/0 4 150 75 125 60 4 2 23 11.5 11.5 5.75

SP Series Roto-Phase
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
SP2 10 12 20 10 20 10 0 0 5 2.5 2.5 1.25
SP3 8 12 30 15 30 15 1 0 4 2 2 1
SP5 8 10 40 20 40 20 2 1 7 3.5 3.5 1.75
SP7 6 10 50 25 45 22.5 2 1 7 3.5 3.5 1.75
SP10 4 8 80 40 60 30 3 2 11 5.5 5.5 2.75
SP15 2 6 125 60 100 50 3 2 18 9 9 4.5
SP20 1/0 4 150 75 125 60* 4 2 23 11.5 11.5 5.75
SP25* 3* 6* 100* 50* 80* 40* 3* 2* 16* 8* 80* 40*
SP30* 2* 6* 125* 60* 100* 50* 3* 2* 18* 9* 110 55*
SP40* 1/0* 4* 150* 75* 125* 60* 4* 2* 23* 11.5* 128* 64*
SP50* 2* 6* 125* 50* 100* 50* 3* 2* 18* 9* 110* 55*
SP60* 1/0* 4* 150* 75* 125* 60* 4* 2* 23* 11.5* 128* 64*
*Indicates units in electrical parallel. Data represents requirements for each unit.

Current Limiting Roto-Phase
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
HD7CL 6 10 50 25 45 22.5 2 1 7 3.5 40 20
HD10CL 4 8 80 40 60 30 3 2 11 5.5 61 30.5
HD15CL 3 6 100 50 80 40 3 2 16 8 80 40
HD20CL 2 6 125 60 100 50 3 2 18 9 110 55
HD25CL 1/0 4 150 75 125 60 4 2 23 11.5 128 64
HD30CL 2/0 3 150 75 150 75 5 3 30 15 150 75
HD40CL 4/0 2 200 100 200 100 5 4 40 20 200 100
HD50CL 350 1/0 250 125 250 125 5 4 50 25 250 125
HD60CL 500 2/0 300 150 300 150 6 5 60 30 300 150
HD75CL 750 4/0 400 200 400 200 6 5 80 40 400 200
HD100CL 1250 350 500 250 500 250 6 5 100 50 500 250

Passenger and Freight Elevator Roto-Phase
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
CHD5ELV 8 10 40 20 40 20 2 1 7 3.5 33 16.5
CHD7ELV 6 10 50 25 45 22.5 2 1 7 3.5 40 20
CHD10ELV 4 8 80 40 60 30 3 2 11 5.5 61 30.5
CHD15ELV 3 6 100 50 80 40 3 2 16 8 80 40
CHD20ELV 2 6 125 60 100 50 3 2 18 9 110 55
CHD25ELV 1/0 4 150 75 125 60 4 2 23 11.5 128 64
CHD30ELV 1/0 4 150 75 125 60 4 2 23 11.5 128 64
CHD40ELV 1/0 4 150 75 125 60 4 2 23 11.5 128 64

TM Series Roto-Phase
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
TM5 6 10 50 25 45 22.5 2 1 10 5 26 13
TM7 6 10 50 25 45 22.5 2 1 10 5 26 13
TM10 4 8 80 40 60 30 3 2 12 6 28 14
TM15 3 6 100 50 80 40 3 2 16 8 60 30
TM20 1/0 4 150 75 125 60 4 2 22 11 86 43

Computer Load Roto-Phase
Wire Size
T1-T2-T3
Fuse Size Overload Protection Magnetic Starter No-Load Amperage Capacitor Amperage
Voltage Voltage Voltage Voltage Avg. Voltage Avg. Voltage
Model: 230 460 230 460 230 460 230 460 230 460 230 460
COMP1 8   30   30   1   6   11  
COMP2 8   40   40   2   8   24  
COMP3 6   50   45   2   10   26  
COMP4 4   80   60   3   12   28  
COMP5 3   100   80   3   16   60  
COMP6 2   125   100   3   18   110  
COMP7 1/0   150   125   4   23   128  

Contact ARCO

Home Office:
2325 E. Michigan Road
Shelbyville, IN 46176-3400
Toll Free: 800-428-4370
Direct: 317-398-9713
Fax: 317-398-2655
Location Manager:
E-Mail: Hal Pike
Sales Manager:
E-Mail: Tim Drake